4.4 Electrical Data - 525-690 VMains Supply 3 x 525- 690 VACAutomationDrive FC 302 P11K P15K P18K P22KHigh/ Normal Load* HO NO HO NO HO NO HO NOTypical Shaft output at 550V [kW] 7.5 11 11 15 15 18.5 18.5 22Typical Shaft output at 575V [HP] 11 15 15 20 20 25 25 30Typical Shaft output at 690V [kW] 11 15 15 18.5 18.5 22 22 30Enclosure IP21, 55 B2 B2 B2 B2Output currentContinuous(3 x 525-550 V) [A] 14 19 19 23 23 28 28 36Intermittent (60 sec over-load)(3 x 525-550 V) [A]22.4 20.9 30.4 25.3 36.8 30.8 44.8 39.6Continuous(3 x 551-690 V) [A] 13 18 18 22 22 27 27 34Intermittent (60 sec over-load)(3 x 551-690 V) [A]20.8 19.8 28.8 24.2 35.2 29.7 43.2 37.4Continuous KVA(at 550 V) [KVA] 13.3 18.1 18.1 21.9 21.9 26.7 26.7 34.3Continuous KVA(at 575 V) [KVA] 12.9 17.9 17.9 21.9 21.9 26.9 26.9 33.9Continuous KVA(at 690 V) [KVA] 15.5 21.5 21.5 26.3 26.3 32.3 32.3 40.6Max. input currentContinuous(3 x 525-690 V) [A] 15 19.5 19.5 24 24 29 29 36Intermittent (60 sec over-load)(3 x 525-690 V) [A]23.2 21.5 31.2 26.4 38.4 31.9 46.4 39.6Max. cable size, mains,motor, load share andbrake [mm 2 (AWG)]35 (1/0)Max. external mains fuses[A] 1 63 63 63 63Estimated power lossat rated max. load [W] 4) 228 285 335 375Weight,enclosure IP21, IP 55 [kg] 27Efficiency4) 0.98 0.98 0.98 0.98* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s4 AutomationDrive FC 300 Selection FC 300 Design Guide70 MG.33.BC.02 - VLT® is a registered Danfoss trademark4