4 AutomationDrive FC 300 Selection4.1 Electrical Data - 200-240 VMains Supply 3 x 200 - 240 VACAutomationDrive FC 301/AutomationDrive FC 302 PK25 PK37 PK55 PK75 P1K1 P1K5 P2K2 P3K0 P3K7Typical Shaft Output [kW] 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 3.7Enclosure IP 20/IP 21 A2 A2 A2 A2 A2 A2 A2 A3 A3Enclosure IP 20(AutomationDrive FC 301 only) A1 A1 A1 A1 A1 A1 - - -Enclosure IP 55, 66 A5 A5 A5 A5 A5 A5 A5 A5 A5Output currentContinuous(3 x 200-240 V ) [A] 1.8 2.4 3.5 4.6 6.6 7.5 10.6 12.5 16.7Intermittent(3 x 200-240 V ) [A] 2.9 3.8 5.6 7.4 10.6 12.0 17.0 20.0 26.7ContinuousKVA (208 V AC) [KVA] 0.65 0.86 1.26 1.66 2.38 2.70 3.82 4.50 6.00Max. cable size (mains, motor,brake) [mm 2 (AWG 2))] 0.2 - 4 (24 - 10)Max. input currentContinuous(3 x 200-240 V ) [A] 1.6 2.2 3.2 4.1 5.9 6.8 9.5 11.3 15.0Intermittent(3 x 200-240 V ) [A] 2.6 3.5 5.1 6.6 9.4 10.9 15.2 18.1 24.0Max. mains fuses1) [A] 10 10 10 10 20 20 20 32 32EnvironmentEstimated power lossat rated max. load [W] 4) 21 29 42 54 63 82 116 155 185Weight, enclosure IP20 [kg] 4.7 4.7 4.8 4.8 4.9 4.9 4.9 6.6 6.6A1 (IP20) 2.7 2.7 2.7 2.7 2.7 2.7 - - -A5 (IP55, 66) 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5 13.5Efficiency 4) 0.94 0.94 0.95 0.95 0.96 0.96 0.96 0.96 0.960.25 - 3.7 kW only available as 160% high overload.Mains Supply 3 x 200- 240 VACAutomationDrive FC 301/AutomationDrive FC 302 P5K5 P7K5 P11KHigh/ Normal Load* HO NO HO NO HO NOTypical Shaft Output [kW] 5.5 7.5 7.5 11 11 15Enclosure IP20 B3 B3 B4Enclosure IP21 B1 B1 B2Enclosure IP55, 66 B1 B1 B2Output currentContinuous(3 x 200-240 V) [A] 24.2 30.8 30.8 46.2 46.2 59.4Intermittent(60 sec overload)(3 x 200-240 V) [A]38.7 33.9 49.3 50.8 73.9 65.3ContinuousKVA (208 V AC) [KVA] 8.7 11.1 11.1 16.6 16.6 21.4Max. input currentContinuous(3 x 200-240 V ) [A] 22 28 28 42 42 54Intermittent(60 sec overload)(3 x 200-240 V ) [A]35.2 30.8 44.8 46.2 67.2 59.4Max. cable size [mm2 (AWG)] 2) 16 (6) 16 (6) 35 (2)Max cable size with mains discon-nect 16 (6)Max. mains fuses [A] 1 63 63 80Estimated power lossat rated max. load [W] 4) 239 310 371 514 463 602Weight,enclosure IP21, IP 55, 66 [kg] 23 23 27Efficiency4) 0.964 0.959 0.964* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 sFC 300 Design Guide 4 AutomationDrive FC 300 SelectionMG.33.BC.02 - VLT® is a registered Danfoss trademark 594