12.2 Wiring Configurations for AnalogSpeed ReferenceParameters+10 VA INA INCOMA OUTCOM505354554239A53U - I0 – 10 V+-e30bb926.11FCFunction SettingParameter 6-10 Terminal 53 LowVoltage0.07 V*Parameter 6-11 Terminal 53 HighVoltage10 V*Parameter 6-14 Terminal 53 LowRef./Feedb. Value0 RPMParameter 6-15 Terminal 53 HighRef./Feedb. Value1500 RPM*=Default valueNotes/comments:Table 12.3 Wiring Configuration for Analog Speed Reference(Voltage)Parameters+10 VA INA INCOMA OUTCOM505354554239+-FCe30bb927.11A53U - I4 - 20mAFunction SettingParameter 6-12 Terminal 53 LowCurrent4 mA*Parameter 6-13 Terminal 53 HighCurrent20 mA*Parameter 6-14 Terminal 53 LowRef./Feedb. Value0 RPMParameter 6-15 Terminal 53 HighRef./Feedb. Value1500 RPM*=Default valueNotes/comments:Table 12.4 Wiring Configuration for Analog Speed Reference(Current)12.3 Wiring Configurations for Start/StopParametersFC+24 V+24 VD IND IND INCOMD IND IND IND IN+10A INA INCOMA OUTCOM12131819202729323337505354554239130BB802.10Function SettingParameter 5-10 Terminal 18Digital Input[8] Start*Parameter 5-12 Terminal 27Digital Input[0] NooperationParameter 5-19 Terminal 37 SafeStop[1] SafeTorque OffAlarm*=Default valueNotes/comments:If parameter 5-12 Terminal 27Digital Input is set to [0] Nooperation, a jumper wire toterminal 27 is not needed.Table 12.5 Wiring Configuration for Start/Stop Command withSafe Torque Off130BB805.12SpeedStart/Stop (18)Illustration 12.1 Start/Stop with Safe Torque OffApplication Examples VLT® AQUA Drive FC 202110 Danfoss A/S © 05/2017 All rights reserved. MG22B1021212