Digital input/output terminalsTerminal Parameter DefaultsettingDescription27 Parameter 5-12Terminal 27Digital Input[2] CoastinverseFor digital input oroutput. Defaultsetting is input.29 Parameter 5-13Terminal 29Digital Input[14] JOG20 – – Common for digitalinputs and 0 Vpotential for 24 Vsupply.37 – STO When not using theoptional STO feature,a jumper wire isrequired betweenterminal 12 (or 13)and terminal 37. Thisset-up allows thedrive to operate withfactory defaultprogramming values.Table 10.6 Digital Input/Output Terminal DescriptionsAnalog input/output terminalsTerminal Parameter DefaultsettingDescription39 – – Common for analogoutput.42 Parameter 6-50Terminal 42Output[0] NooperationProgrammable analogoutput. 0–20 mA or4–20 mA at amaximum of 500 Ω.50 – +10 V DC 10 V DC analogsupply voltage forpotentiometer orthermistor. 15 mAmaximum.53 Parametergroup 6-1*Analog Input 1Reference Analog input. Forvoltage or current.Switches A53 andA54 select mA or V.54 Parametergroup 6-2*Analog Input 2Feedback55 – – Common for analoginput.Table 10.7 Analog Input/Output Terminal DescriptionsRelay terminals:RELAY 1 RELAY 201 02 03 04 05 06130BF156.10Illustration 10.7 Relay 1 and Relay 2 Terminals• Relay 1 and relay 2. The location of the outputsdepends on the drive configuration. See theoperating guide.• Terminals on built-in optional equipment. See theinstructions provided with the equipment option.Electrical Installation Con... VLT® AQUA Drive FC 20278 Danfoss A/S © 05/2017 All rights reserved. MG22B1021010