380–480 VPower size [kW (hp)] Cable [m (ft)] Mains voltage[V]Rise time [μs] Peak voltage [V] dU/dt [V/μs]355–450 (500–600) 5 (16) 460 0.23 1038 237230 (98) 460 0.72 1061 644150 (492) 460 0.46 1142 1160300 (984) 460 1.84 1244 283500–560 (650–750) 5 (16) 460 0.42 1042 129530 (98) 460 0.57 1200 820150 (492) 460 0.63 1110 844300 (984) 460 2.21 1175 239Table 10.16 NEMA dU/dt Test Results for E1h–E4h with Unshielded Cables and No Output Filter, 380–480 VPower size [kW (hp)] Cable [m (ft)] Mains voltage[V]Rise time [μs] Peak voltage [V] dU/dt [V/μs]355–450 (500–600) 5 (16) 460 0.33 1038 255630 (98) 460 1.27 1061 668150 (492) 460 0.84 1142 1094300 (984) 460 2.25 1244 443500–560 (650–750) 5 (16) 460 0.53 1042 156930 (98) 460 1.22 1200 1436150 (492) 460 0.90 1110 993300 (984) 460 2.29 1175 411Table 10.17 IEC dU/dt Test Results for E1h–E4h with Unshielded Cables and No Output Filter, 380–480 VPower size [kW (hp)] Cable [m (ft)] Mains voltage[V]Rise time [μs] Peak voltage [V] dU/dt [V/μs]355–450 (500–600) 5 (16) 460 0.17 1017 317630 (98) 460 – – –150 (492) 460 0.41 1268 1311500–560 (650–750) 5 (16) 460 0.17 1042 312630 (98) 460 – – –150 (492) 460 0.22 1233 2356Table 10.18 NEMA dU/dt Test Results for E1h–E4h with Shielded Cables and No Output Filter, 380–480 VPower size [kW (hp)] Cable [m (ft)] Mains voltage[V]Rise time [μs] Peak voltage [V] dU/dt [V/μs]355–450 (500–600) 5 (16) 460 0.26 1017 312830 (98) 460 – – –150 (492) 460 0.70 1268 1448500–560 (650–750) 5 (16) 460 0.27 1042 313230 (98) 460 – – –150 (492) 460 0.52 1233 1897Table 10.19 IEC dU/dt Test Results for E1h–E4h with Shielded Cables and No Output Filter, 380–480 VElectrical Installation Con... VLT® AQUA Drive FC 20288 Danfoss A/S © 05/2017 All rights reserved. MG22B1021010