7 Specifications7.1 Electrical Data, 380–480 VVLT® AQUA Drive FC 202 N355 N400 N450High/normal load HO NO HO NO HO NO(High overload=150% current during 60 s,normal overload=110% current during 60 s)Typical shaft output at 400 V [kW] 315 355 355 400 400 450Typical shaft output at 460 V [hp] 450 500 500 600 550 600Enclosure size E1h/E3h E1h/E3h E1h/E3hOutput current (3-phase)Continuous (at 400 V) [A] 600 658 658 745 695 800Intermittent (60 s overload)(at 400 V) [A] 900 724 987 820 1043 880Continuous (at 460/500 V) [A] 540 590 590 678 678 730Intermittent (60 s overload)(at 460/500 V) [A] 810 649 885 746 1017 803Continuous kVA (at 400 V) [kVA] 416 456 456 516 482 554Continuous kVA (at 460 V) [kVA] 430 470 470 540 540 582Maximum input currentContinuous (at 400 V) [A] 578 634 634 718 670 771Continuous (at 460/500 V) [A] 520 569 569 653 653 704Maximum number and size of cablesper phase (E1h)- Mains and motor without brake [mm2 (AWG)]1) 5x240 (5x500 mcm) 5x240 (5x500 mcm) 5x240 (5x500 mcm)- Mains and motor with brake [mm2 (AWG)1) 4x240 (4x500 mcm) 4x240 (4x500 mcm) 4x240 (4x500 mcm)- Brake or regeneration [mm2 (AWG)1) 2x185 (2x350 mcm) 2x185 (2x350 mcm) 2x185 (2x350 mcm)Maximum number and size of cablesper phase (E3h)- Mains and motor without brake [mm2 (AWG)]1) 6x240 (6x500 mcm) 6x240 (6x500 mcm) 6x240 (6x500 mcm)- Mains and motor with brake [mm2 (AWG)1) 2x185 (2x350 mcm) 2x185 (2x350 mcm) 2x185 (2x350 mcm)- Load share or regeneration [mm2 (AWG)1) 4x185 (4x350 mcm) 4x185 (4x350 mcm) 4x185 (4x350 mcm)Maximum external mains fuses [A]2) 800 800 800Estimated power loss at 400 V [W]3) 4) 6178 6928 6851 8036 7297 8783Estimated power loss at 460 V [W] 3) 4) 5322 5910 5846 6933 7240 7969Efficiency4) 0.98 0.98 0.98Output frequency 0–590 Hz 0–590 Hz 0–590 HzHeat sink overtemperature trip [°C (°F)] 110 (230) 110 (230) 110 (230)Control card overtemperature trip [°C (°F)] 80 (176) 80 (176) 80 (176)Power card overtemperature trip [°C (°F)] 85 (185) 85 (185) 85 (185)Fan power card overtemperature trip [°C (°F)] 85 (185) 85 (185) 85 (185)Active in-rush card overtemperature trip[°C (°F)] 85 (185) 85 (185) 85 (185)Table 7.1 Technical Specifications, Mains Supply 3x380–480 V ACSpecifications VLT® AQUA Drive FC 20232 Danfoss A/S © 05/2017 All rights reserved. MG22B10277