12.4 Wiring Configuration for an ExternalAlarm ResetParametersFC+24 V+24 VD IND IND INCOMD IND IND IND IN+10 VA INA INCOMA OUTCOM12131819202729323337505354554239130BB928.11Function SettingParameter 5-11 Terminal 19Digital Input[1] Reset*=Default valueNotes/comments:Table 12.8 Wiring Configuration for an External Alarm Reset12.5 Wiring Configuration for SpeedReference Using a ManualPotentiometerParameters+10 VA INA INCOMA OUTCOM505354554239A53U - I≈ 5kΩ e30bb683.11FCFunction SettingParameter 6-10 Terminal 53 LowVoltage0.07 V*Parameter 6-11 Terminal 53 HighVoltage10 V*Parameter 6-14 Terminal 53 LowRef./Feedb. Value0 RPMParameter 6-15 Terminal 53 HighRef./Feedb. Value1500 RPM*=Default valueNotes/comments:Table 12.9 Wiring Configuration for Speed Reference(Using a Manual Potentiometer)12.6 Wiring Configuration for Speed Up/Speed DownParametersFC+24 V+24 VD IND IND INCOMD IND IND IND IN12131819202729323337e30bb804.12Function SettingParameter 5-10 Terminal 18Digital Input[8] Start*Parameter 5-12 Terminal 27Digital Input[19] FreezeReferenceParameter 5-13 Terminal 29Digital Input[21] Speed UpParameter 5-14 Terminal 32Digital Input[22] SpeedDown*=Default valueNotes/comments:Table 12.10 Wiring Configuration for Speed Up/Speed Down130BB840.12SpeedReferenceStart (18)Freeze ref (27)Speed up (29)Speed down (32)Illustration 12.3 Speed Up/Speed DownApplication Examples VLT® AQUA Drive FC 202112 Danfoss A/S © 05/2017 All rights reserved. MG22B1021212