NOTICEWhen changing the function of S201, S202, or S801 donot to use force during the switch over. Remove the LCPfixture (cradle) when operating the switches. Do notoperate the switches when the frequency converter ispowered.130BT310.11Illustration 4.29 Switch Location4.4 Final Set-up and TestTo test the set-up and to ensure that the frequencyconverter is running, follow these steps.Step 1. Locate the motor nameplateNOTICEThe motor is either star (Y) or delta connected (Δ). Thisinformation is on the motor nameplate.THREE PHASE INDUCTION MOTORkW 400MOD MCV 315E Nr. 135189 12 04PRIMARYSECONDARYV 690 AV AV AV A410.6 CONN YCONNCONNCONN ENCLOSURECAUTIONCOS fALTRISEmSF 1.150.85AMB 40100080°C°CIP2340IL/IN 6.5HP 536mm 1481HzDESIGN50NDUTYINSUL WEIGHT 1.83 tonEFFICIENCY % 95.8% 95.8% 75%100%S1I130BA767.10Illustration 4.30 NameplateStep 2. Enter the motor nameplate data in thisparameter list.To access this list, press [Quick Menu] then select Q2 QuickSetup.1. 1-20 Motor Power [kW]1-21 Motor Power [HP]2. 1-22 Motor Voltage3. 1-23 Motor Frequency4. 1-24 Motor Current5. 1-25 Motor Nominal SpeedStep 3. Activate the Automatic Motor Adaptation (AMA)Performing an AMA ensures optimum performance. TheAMA measures the values from the motor modelequivalent diagram.1. Connect terminal 37 to terminal 12 (if terminal 37is available).2. Connect terminal 27 to terminal 12 or set5-12 Terminal 27 Digital Input to [0] No function.3. Activate the AMA 1-29 Automatic MotorAdaptation (AMA).4. Select between complete or reduced AMA. If asine-wave filter is mounted, run only the reducedAMA, or remove the sine-wave filter during theAMA procedure.How to Install Operating Instructions48 Danfoss A/S © Rev. 06/2014 All rights reserved. MG20Y20244 PreviousNext |