1Table 11. Relative humidity specificationsRelative humidity SpecificationsStorage 5% to 95% RH with 33°C (91°F) maximum dew point.Atmosphere must be noncondensing always.Operating 10% to 80% Relative Humidity with 29°C (84.2°F) maximumdew point.Table 12. Maximum vibration specificationsMaximum vibration SpecificationsOperating 0.26 Grms at 5 Hz to 350 Hz (all operation orientations).Storage 1.88 Grms at 10 Hz to 500 Hz for 15 min (all six sides tested).Table 13. Maximum shock specificationsMaximum shock SpecificationsOperating Six consecutively run shock pulses in the positive and negativex, y, and z axes of 40 G for up to 2.3 ms.Storage Six consecutively run shock pulses in the positive and negativex, y, and z axes (one pulse on each side of the system) of 71 Gfor up to 2 ms.Table 14. Maximum altitude specificationsMaximum altitude SpecificationsOperating 3048 m (10,000 ft).Storage 12,000 m (39,370 ft).Table 15. Operating temperature derating specificationsTemperature SpecificationsUp to 35 °C (95 °F) Maximum temperature is reduced by 1°C/300 m (1°F/547 ft)above 950 m(3,117 ft).35 °C to 40 °C (95 °F to 104 °F) Ma ximum t emper a tur e is r educed by 1°C /175 m (1°F/ 3 19 ft)above 950 m (3,117 ft).40 °C to 45 °C (104 °F to 113 °F) Maximum temperature is reduced by 1°C/125 m (1°F/228 ft)above 950 m(3,117 ft).Particulate and gaseous contamination specificationsThe following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseouscontamination. If the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage orfailure, you may need to rectifythe environmental conditions. Remediation of environmental conditions is the responsibility of thecustomer.Table 16. Particulate contamination specificationsParticulatecontamination SpecificationsAir filtration Datacenterairfiltrationasdefinedby ISOClass 8 per ISO14644-1with a 95% upper confidence limit.