UPS OPERATING INSTRUCTIONSEaton 9395 UPS (450–825 kVA) Installation and Operation Manual 164201725 Rev 4 www.eaton.com/powerquality7-12Table 7‐5. Command Menu OperationFunction Subfunction OperationUPS ControlCommandsUse the up or down arrow pushbutton to highlight the command function desired,then press the SELECT pushbutton to execute the command or proceed to furthercommand screens.Go to Online Starts the UPS in Online mode or transfers the UPS to Online mode from Bypassmode.Enable (Disable) Energy Saver Enables or disables Energy Saver System mode. Enable changes to Disable when theEnergy Saver System mode is enabled.Enable (Disable) Var ModuleManagementEnables or disables the Variable Module Management System mode. Enable changesto Disable when the Variable Module Management System mode is enabled.Start High Alert Starts High Alert mode.Go to Bypass Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Onlinemode.Load Off Displays the Load Off screen (see paragraph 7.2.7).BypassCommandsUse the up or down arrow pushbutton to highlight the command function desired,then press the SELECT pushbutton to execute the command or proceed to furthercommand screens.Go to Bypass Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Onlinemode.Go to Online Starts the UPS in Online mode or transfers the UPS to Online mode from Bypassmode.Enable (Disable) Energy Saver Enables or disables Energy Saver System mode. Enable changes to Disable when theEnergy Saver System mode is enabled.Enable (Disable) Var ModuleManagementEnables or disables the Variable Module Management System mode. Enable changesto Disable when the Variable Module Management System mode is enabled.Start High Alert Starts High Alert mode.Load Off Displays the Load Off screen (see paragraph 7.2.7).Charger ControlCommandsUse the up or down arrow pushbutton to highlight the command function desired,then press the SELECT pushbutton to execute the command.Charger On Turns the battery charger on.Charger Off Turns the battery charger off.UPM ControlCommandsUse the up or down arrow pushbutton to highlight the command function desired,then press the SELECT pushbutton to execute the command.UPM On Turns the UPM on without transferring the load to Online mode. The Load is onbypass.UPM Off Transfers the load to bypass and turns the UPM off.UPM Go to Online Turns the UPM on and transfers the load to Online mode.Charger On Turns the battery charger on.Charger Off Turns the battery charger off.NOTE The Energy Saver System and Variable Module Management System mode commands are displayed only if enabled at the factory or by an EatonCustomer Service Engineer.NOTE Variable Module Management System and Energy Saver System modes are mutually exclusive.