UPS INSTALLATION PLAN AND UNPACKINGEaton 9395 UPS (450–825 kVA) Installation and Operation Manual 164201725 Rev 4 www.eaton.com/powerquality3-22Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). SeeTable 3‐15 for conduit requirements.Per NEC article 300, 3(B)(1), all three‐phase conductors must be run in the sameconduit. Neutral and ground must be run in the same conduit as the phaseconductors.Conduit is sized to accommodate one neutral conductor the same size as the phaseconductor and one ground conductor sized in accordance with NEC Table 250.122.Conduit sizes listed are for copper wiring only.Table 3‐15. Power Cable Conduit RequirementsUPS Model Voltage Terminal Number of Wiresin ConduitMinimum ConduitTrade SizeNumber ofConduitsEaton 9395-825/650400 VacAC Input to UPS Rectifier(A, B, C, Ground) 4 3 4AC Input to UPS Rectifier (Separate Feed)(A, B, C, Ground) 4 2 3(Each UPM)AC Input to Bypass and Output (Four Wire)(A, B, C, Ground) 4 3 3AC Input to Bypass and Output (Five Wire)(A, B, C, Neutral, Ground) 5 3 4480 VacAC Input to UPS Rectifier(A, B, C, Ground) 4 3 3AC Input to UPS Rectifier (Separate Feed)(A, B, C, Ground) 4 2 2(Each UPM)AC Input to Bypass and Output (Four Wire)(A, B, C, Ground) 4 2‐1/2 3AC Input to Bypass and Output (Five Wire)(A, B, C, Neutral, Ground) 5 3 4DC Battery(Positive, Negative, Ground) See Note 1Eaton 9395-825/750400 VacAC Input to UPS Rectifier(A, B, C, Ground) 4 3 4AC Input to UPS Rectifier (Separate Feed)(A, B, C, Ground) 4 2 3(Each UPM)AC Input to Bypass and Output (Four Wire)(A, B, C, Ground) 4 3 4AC Input to Bypass and Output (Five Wire)(A, B, C, Neutral, Ground) 5 3 5480 VacAC Input to UPS Rectifier(A, B, C, Ground) 4 3 4AC Input to UPS Rectifier (Separate Feed)(A, B, C, Ground) 4 2 2(Each UPM)AC Input to Bypass and Output (Four Wire)(A, B, C, Ground) 4 3 3AC Input to Bypass and Output (Five Wire)(A, B, C, Neutral, Ground) 5 3 4DC Battery(Positive, Negative, Ground) See Note 1