InstallationEaton 93PM Integrated Battery Cabinet-Small Welded (IBC-SW) Installation Manual P-164000639—Rev 1 www.eaton.com/powerquality 4-39. After the IBC–SW is resting on the floor, remove the jacking bolts and floor protectors. Recycle them in aresponsible manner.Figure 4-1. Removing the Pallet Skids and Supports – Eaton 93PM Integrated Battery Cabinet–Small Welded10. Remove the cabinet support bolts fastening the front, rear, and side cabinet supports together andremove the side supports (see Figure 4-1).11. Remove the cabinet mounting bolts holding the front and rear supports to the cabinet base and removethe supports (see Figure 4-1).12. If installing the cabinet permanently, retain the cabinet mounting bolts; otherwise, recycle the bolts alongwith the support brackets in a responsible manner.13. Attach the front cover by placing the cover on the two mounting bolts on the bottom and installing the twomounting bolts on the top. Tighten all of the bolts.14. If the leveling feet are not retracted, turn all four leveling feet until they are retracted as far into the cabinetas possible.15. If line-up-and-match installation, remove the rectangular and circular knockout on the bottom and top frontside of the UPS and the IBC–SW (see Figure 4-2).Jacking Bolt s(2 places front)(2 places rear)Pallet SkidSkid Mounting Bolts(4 places front)(4 places rear)Floor Protectors(2 places front)(2 places rear)CabinetMounting Bolts(4 places front)(4 places rear)Front CabinetSupportRear CabinetSupportLeft SideCabinet SupportRight SideCabinet SupportCabinetSupport Bolts(2 places ateach corner)NOTE The battery cabinet may be located to either the right or left of the UPS cabinet.This procedure assumes the battery cabinet is located to the right of the UPScabinet.