CL-7 control in General Electric control boxwith fork-type terminalTable 4 Kit parts identificationItem Description Part Number Qty1 CL-7 PRA wiring harness,General Electric fork-type terminalA64316200G 12 Hinge bracket assembly E0003X00G22 13 Left side bracket E0003X00G25 14 Self adjusting latch E0003X00G158 1Required tools●● Screwdriver (standard)●● Screwdriver (Phillips head)●● 3/8-Inch nut driver or combination wrenchotee:N Verify all kit items are present before beginninginstallation procedure.Installation procedureFollow these instructions to install the CL-7 PRA on avoltage regulator manufactured by General Electric withfork-type terminal connections.1. Remove existing control per the manufacturer‘srequirements. Retain the hinge pins.otee:N If the General Electric wiring harness (Figure 26),hinge bracket and latch bracket (Figure 28) havealready been installed on the new CL-7 control,proceed to Step 11.otee:N The GE harness may be equipped with two wirescolored white and white/blue with two-terminalconnectors as shown in Figure 26. The wiresare for connection to the CL-7 control generalpurpose inputs (GPIs). The wires can be used foranalog voltage reduction or other programmablefunctionality. See document MN225003EN, CL-7Voltage Regulator Control Installation, Operation, andMaintenance Instructions for more information onthe GPIs.Figure 26 Item 1, General Electric fork-terminal wireharness2. Using a screwdriver, remove the four screws touninstall the existing latch bracket from the left side ofthe CL-7 control; retain the screws. See Figure 27.Figure 27 Removal of latch bracket from CL-7 control3. Install the General Electric latch bracket (Item 3) on theleft side of the control using the screws retained fromthe last step. See Figure 28.10CL-7 Control Panel RetrofitInstallatIon InstructIons MN225018EN April 2018