CL-7 control in Eaton control box, not deadfrontTable 2 Kit parts identificationItem Description Part Number Qty1 Wiring harness assembly,Fanning strip styleA64316200E 12 18-position terminal board kit A64289100B 13 Terminal jumper TAA114731001 24 Jumper wire 102A008HEHE043 1otee:N Eaton‘s Universal PRA kit may include parts notrequired for every installation. Only parts required forthis installation are included in this list.Required tools●● Screwdriver (Standard)●● Screwdriver (Phillips)otee:N Verify all kit items are present before beginninginstallation procedure.Installation procedureFollow these instructions to install the CL-7 PRA into acontrol box on an Eaton voltage regulator with a fanningstrip terminal board connection.1. Remove the existing control. Refer to the appropriatevoltage regulator control manual for completeinstructions on removing a control.For example, refer to Service Information S225-10-10,McGraw-Edison® VR-32 Regulator and CL-5 SeriesControl Installation, Operation and MaintenanceInstructions for information on the CL-5 series voltageregulator control.2. If the control box contains a 10-position TB1 terminalboard (see Figure 8), it must be upgraded to an18-position board. See document MN225019EN,Back Panel Upgrade 10- to 18-Position Terminal StripInstallation Instructions for instruction on installing the18-position terminal board.Figure 8 Obsolete 10-position terminal board to bereplaced3. If the control box is already equipped with the18-position terminal board, it must be reconfigured tothe correct jumper configuration. A metal jumper isrequired between terminal 3 and 4 and a wire jumper isrequired between terminals 2 and G (see Figure 9).Figure 9 Proper jumper arrangement on 18-positionterminal board for the CL-7 voltage regulator control4. If a jumper is present between terminals 4 and 5 ofTB8 (see Figure 10), remove the jumper. If this jumperremains in place, the CL-7 control will display an AutoTap Blocked indication.Figure 10 Remove metal jumper between terminals 4and 54CL-7 Control Panel RetrofitInstallatIon InstructIons MN225018EN April 2018