Intelligent Technologies (IT.) D77A I/O Module ProductsMN05002001E For more information visit: www.EatonElectrical.com 43Analog OutputsAnalog signals are typically used to transmit or indicate linear data like pressure or linear actuation, as illustrated in Figure 41. Theanalog output devices to which analog outputs are wired are typically current loop or voltage range devices like 4-20 mA signals or0-10V signals. Refer to Analog Output Module Specifications on page 16 for module details.Note: Ground the shield on one end only. It is recommended to limit the cable impedance by keeping the cable length as short aspossible. Limiting the distance from ground to the shield is also recommended. The recommended cable is a Belden TM 8761 orequivalent.Figure 41: Analog Output Wiringa) Control Transformerb) 24 VDC Power Supplyc) Voltage Output Deviced) Current Output DeviceWire Type Wire Size Terminal TorqueSolid Cu-90°C #14 - # 22 AWG 4.5 in-lbs.Stranded Cu-90°C #16 - # 22 AWG 4.5 in-lbs.H1 H4H3 H224VDC10FU12345678I0C0V1I1C1NCNC9101112-X1 X2120VAC NEU+- +JIC-0008NCNCV0VIabcde-+