11GBExplosion protected LED-Emergency Exit LuminaireSeries: Ex-Lite N; Ex-Lite NLT2 Technical dataEC-Type Examination Certificate: BVS 09 ATEX E 048Marking acc. to 2014/34/EU and standard of seriesEN 60079N tamax + 40 °C: II 2 G Ex e ib mb IIC T5 Gbtamax + 50 °C: II 2 G Ex e ib mb IIC T4 GbNLT tamax + 40 °C: II 2 G Ex d e ib mb IIC T4 GbN/NLT II 2 D Ex tb IIIC T80°C DbIECEx Certificate of Conformity: IECEx BVS 13.0016Category of application standard of series IEC 60079IEC 60079N tamax + 40 °C: Ex e ib mb IIC T5 Gbtamax + 50 °C: Ex e ib mb IIC T4 GbN Ex tb IIIC T80°C DbRated voltageN AC: 110 V - 277 V *DC: 110 V - 250 V *NLT AC: 110 V - 240 V ** max. permissable tolerances accd. IEC/EN 60079-0Frequency: 50 - 60 HzRated currentN 110 V AC/DC: approx. 0.06 A220 V AC/DC: approx. 0.035 ANLT heating: approx. 0.5 A / 50 WBattery module: Accu 2 x 6 V / 0,8 AhCharging time (cap. > 90 %): 24 hDuration of emergency lighting: 3 h (**)(**) Note: New batteries will reach their total useful capacity only after 3 charging/discharging cycles.Insulation class to IEC/EN 61140: IDegree of protection accd. IEC/EN 60529: IP 66Operation temperatureN -20 °C ... +40 °C/+50 °CNLT -40 °C ... +40 °CSpecified data N +5 °C ... +35 °CSpecified data NLT -40 °C ... +35 °CStorage temperature in original packing: -20 °C ... +50 °CWeight: approx. 6.7 kgSupply terminal clamping capacity: 2 x per terminal: 2.5 mm²Ex-e cable entry standard version: 1x M25x1.5 blanking plugStandard version M25 x 1.5suitable cables and test torques of thepressure screwØ cable (mm) NmSeal 1+2+3 1 2 3 min. 8.0 1.5max. (1) 10.0 2.0Seal 1+2 1 2 3 min. 10.0 2.3max. (1) 13.0 2.6Seal 1 1 2 3 min. 13.5 1.3max. (1) 17.5 2.3(1) The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range canvary by using cables with different manufacturing tolerances and material properties. Please use a suitablecombination of seals in the intermediate area, so that the cap nut can be tightened in future maintenancework on the cable entry.Metall version 2x M20x1.5 threadTest torque for screw in thread cable entry:for screw in thread cable entry: 3.0 Nmfor cover screw 2.4 Nmfor screw fixing: 1.4 Nm1 LegendeWarningThis symbol warns of a serious hazard.Failure to observe this warning may resultin death or the destruction of property.CautionThis symbol warns of a possible failure.Failure to observe this caution may resultin the total failure of the device or thesystem or plant to which it is connected.1.1 Safety instructionsFor skilled electricians andqualified personnel in accordancewith national legislation, includingthe relevant standards and, where applica-ble, in acc. with IEC/EN 60079-14 onelectrical apparatus for explosiveatmospheres.– The light fitting must not be operated inzone 0 or 20 hazardous areas!– The technical data indicated on the lightfitting are to be observed!– The requirements of theIEC/EN 60079-31 regarding excessivedust deposits and temperature to beconsidered from the user.– Changes of the design and modificati-ons to the light fitting are not permit-ted!– The light fitting shall be operated asintended and only in undamaged andperfect condition!– Do not keep these operating instruc-tions inside the light fitting duringoperation!The national safety rules and regulationsfor prevention of accidents and thefollowing safety instructions which aremarked with an ( ) in these operatinginstruction, will have to be observed!