Eaton 93PM Integrated Battery Cabinet-Small Welded (IBC-SW) Installation Manual 164000639—Rev 03 55CChhaapptteerr 77 PPrroodduucctt SSppeecciiffiiccaattiioonnssThis section provides the following specifications:• Model Numbers• Battery specifications• Environmental and safety specifications77..11 MMooddeellssThe Integrated Battery Cabinet – Small Welded (IBC–SW) is available in two models to meet the needs of theEaton 93PM UPS product line.Integrated BatteryCabinet (IBC)DC VoltageOutput(Nominal)BatteryNameplateCurrent DescriptionEaton 93PM IntegratedBattery Cabinet-SmallWelded432V 165AIBC for:Eaton 93PM (400/480V) 50 kW UPSEaton 93PM (400/480V) 100 kW UPSEaton 93PM (400/480V) 150 kW UPSEaton 93PM (400/480V) 200 kW UPS480V 158AIBC for:Eaton 93PM-L (208V) 60 kW UPSEaton 93PM-L (208V) 120 kW UPSEaton 93PM-L (208V) 160 kW UPSEaton 93PM-L (208V) 200 kW UPSandEaton 93PM (400/480V) 50 kW UPSEaton 93PM (400/480V) 100 kW UPSEaton 93PM (400/480V) 150 kW UPSEaton 93PM (400/480V) 200 kW UPS77..22 SSppeecciiffiiccaattiioonnssThe following sections detail the battery specifications, battery runtimes, and the environmental and safetyspecifications for the UPS. Specifications are subject to change.77..22..11 BBaatttteerryy SSppeecciiffiiccaattiioonnssIBC-SW Battery Type Eaton PWHR12200W4FR or CSB HRL12200WFR 200 Watts/cell valve-regulated lead-acid (VRLA) with a 3-5 year float service life at 77°F (25°C)Number of Strings IBC–SW (432V) 1 string with 36 BatteriesIBC–SW (480V) 1 string with 40 BatteriesBattery Replacement Must be replaced by a qualified service technicianProtection IBC–SW output protected by 250A circuit breaker.