MIB ObjectsEaton Network Card-MS User’s Guide P-164000100—Rev 1 www.eaton.com/powerquality 66Eaton Pulsar MIBThis section contains an overview of MIB definitions for the following MIB files:l Eaton Pulsar MIB (MGE MIB)l Eaton Pulsar MIB (MGE MIB) for an Environmental Monitoring Probe (EMP)The Network Card-MS implements the reduced Eaton Pulsar MIB (MGE MIB); only the objects listed inTable 23 and Table 24are managed. The entire MIB description is available at www.eaton.com/powerquality.Table 24 lists objects that are managed if there is an optional EMP installed. The Eaton Pulsar MIB trap accesspath is 1.3.6.1.4.1.705.1.xupsTopoMachineCode Integer {13.2.0}xupsTopoUnitNumber Integer {13.3.0}xupsTopoPowerStrategy Integer {13.4.0}Table 23. Eaton Pulsar MIB (MGE MIB) ObjectsMIB Object SNMP Format Add.pathupsmgIdentFamilyName String {1,1,0}upsmgIdentModelName String {1,2,0}upsmgIdentFirmwareVersion String {1,4,0}upsmgIdentSerialNumber String {1,7,0}upsmgConfigLowBatteryTime seconds {4,7,0}upsmgConfigLowBatteryLevel % {4,8,0}upsmgConfigAutoRestart 1 (yes), 2 (no) {4,9,0}upsmgConfigVARating VA {4,12,0}upsmgBatteryRemainingTime seconds {5,1,0}upsmgBatteryLevel % {5,2,0}upsmgBatteryVoltage deciVolts {5,5,0}upsmgBatteryCurrent deciAmps {5,6,0}upsmgBatteryFaultBattery 1 (yes), 2 (no) {5,9,0}upsmgBatteryReplacement 1 (yes), 2 (no) {5,11,0}upsmgBatteryLowBattery 1 (yes), 2 (no) {5,14,0}upsmgBatteryChargerFault 1 (yes), 2 (no) {5,15,0}upsmgBatteryLowCondition 1 (yes), 2 (no) {5,16,0}upsmgInputPhaseNum — {6,1,0}mginputVoltage_1 DeciVolts {6,2,1,2,1,0}mginputVoltage_2 DeciVolts {6,2,1,2,2,0}mginputVoltage_3 DeciVolts {6,2,1,2,3,0}mginputFrequency_1 DeciHz {6,2,1,3,1,0}mginputFrequency_2 DeciHz {6,2,1,3,2,0}mginputFrequency_3 DeciHz {6,2,1,3,3,0}mginputMinimumVoltage — {6,2,1,4,0}mginputMaximumVoltage — {6,2,1,5,0}Table 22. PowerMIB Objects (Continued)MIB Object SNMP Format Add.path