INSTALLATIONEaton 9140 UPS (7.5–10 kVA) User's Guide 164201622 Rev 3 www.eaton.com/powerquality56Table 3. UPS Output Wiring SpecificationsUPS TerminalBlockTerminalPosition UPS Wire Function Terminal WireSize Rating1TighteningTorqueOutput 1 Line / Line 1 Out13.3 mm2 (6 AWG) 1.8 Nm (16 lb in)2 Neutral Out23 Output Ground1 Use 13.3 mm 2 (6 AWG) 90C copper wire minimum. For ease of installation, use appropriately sized ferrules on the endof each wire.2 Line 2 Out (single-phase 208V only).12. Set the phase input selector switch for single-phase or three-phaseinput. See Figure 31 on page 53 for the location of the switch.NOTE The UPS will not operate if the input is wired for single-phase and the selectorswitch is set for three-phase.NOTE If the input is wired for three-phase and the selector switch is set for single-phase,the UPS will operate on single-phase. Operating the UPS in this configuration is NOTrecommended and could result in unintended upstream breaker tripping and overheating ofthe input wiring, if the breaker and wiring are sized for three-phase input.NOTE Resetting the phase input selector switch while the UPS is running has no effect onUPS operation. The UPS reads the position of the switch only when powering on.13. Replace the input and output terminal block covers.14. If your rack has conductors for grounding or bonding of ungroundedmetal parts, connect the ground cable (not included) to the groundbonding screw. See Figure 28 on page 50 for the location of theground bonding screw.NOTE DO NOT protect laser printers with the UPS because of the exceptionally high powerrequirements of the heating elements.NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent anoverload alarm.15. Plug the equipment to be protected into the UPS outputreceptacles, but do not turn on the protected equipment (seeFigure 28 on page 50).16. Make any necessary provisions for cord retention and strain relief.