OPERATIONEaton 9140 UPS (7.5–10 kVA) User's Guide 164201622 Rev 3 www.eaton.com/powerquality 63Display FunctionsWhen the UPS starts up, the LCD displays the Eaton logo and the typeof UPS.About 5 seconds after startup or after 15 minutes of inactivity, the LCDdisplays the system status screen. The system status screen shows theoutput voltage, output frequency, output load percent, and the currentoperating mode (see Figure 36 on page 61).The backlit LCD automatically dims after a long period of inactivity. Pressany button to restore the screen.From the system status screen, press the button to select MENU.Use the two middle buttons ( and ) to scroll through the menustructure. Press the button to select an option or enter a submenu.Press the button to cancel or return to the previous menu.The following table shows the basic menu structure.Table 4. Menu Map for Display FunctionsMain Menu Submenu Display Information or Menu FunctionControl Output Control Turn the UPS on and off / Transfer to other modesBattery Test Cancel a test / Schedule a test / View a test reportStatus Active Alarms Display any active alarmsUPS Output Display the voltage, current, frequency, load, current, watts, and VAUPS Input Display the current utility voltage and frequencyBattery Display the current positive and negative battery voltages, percent batterycharge, and expected battery runtime in minutesDC Link Display the current positive and negative rail voltagesSystem Display the system runtime (days/hrs/min/sec)Alarm History Display the most recent 50 events and alarms, by description, alarmnumber, and time (day/hr/mins/sec in system runtime).Model Info UPS Type / UPS Serial Number / UPS Part Number / Firmware VersionSetup User Setup See Table 5 for detail.Service Setup This screen is password-protected.