OPERATIONEaton 9140 UPS (7.5–10 kVA) User's Guide 164201622 Rev 3 www.eaton.com/powerquality64User SettingsThe following table displays the options that can be changed by theuser.Table 5. User SettingsDescription Available Settings Default SettingO/P (Output) Frequency* [50 Hz][60 Hz][Auto]NOTE If Auto is selected, input frequencies<55 Hz are set to 50 Hz, and input frequencies>55 Hz are set to 60 Hz. O/P Frequencychanges from Auto to the sensed frequencysetting.AutoO/P (Output) Voltage [200V][208V][220V][230V][240V][Auto]NOTE If Auto is selected, input voltages<220V are set to 208V, and input voltages>220V are set to 230V. O/P Voltage changesfrom Auto to the sensed voltage setting.AutoBuzzer Alarm [Enabled][Disabled] EnabledBattery Pack 1 through 5NOTE A value of 1 indicates the UPS internalbatteries only. See “Configuring the UPS forEBMs” on page 72.1Battery Test [Enabled][Disabled]NOTE When Enabled, the battery test runsautomatically approximately every threemonths.EnabledDC Start [Enabled][Disabled] Shipped: DisabledAfter one startup andshutdown sequence: EnabledAuto Restart [Enabled][Disabled] EnabledUPS ID 0 through 3NOTE This option is not used.0* Changes to these options should be made before turning on the UPS (while the UPS is in Standby mode); otherwise,the changes do not take effect.