POWER WIRING INSTALLATION NOTES081505C164201554---5NOTE: Customer ground can be run in any conduit listed in Table J.5 of 15DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:Installation InformationA-16 EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.comTable I. UPS Cabinet Power Cable Terminations for the Powerware 9390---120/100,9390---120/120, 9390---160/100, 9390---160/120 and 9390---160/160(480V Input and 480V Output)Terminal Function Terminal Function Size of PressureTerminationTighteningTorqueNm (lb in)TypeScrewAC Input to UPS Rectifierand Bypass(Single Input)E6 Phase A 2 --- #6---250 42.4 (375) 5/16 in. HexE7 Phase B 2 --- #6---250 42.4 (375) 5/16 in. HexE8 Phase C 2 --- #6---250 42.4 (375) 5/16 in. HexAC Input to UPS Rectifier(Dual Input)E1 Phase A 2 --- #6---250 42.4 (375) 5/16 in. HexE2 Phase B 2 --- #6---250 42.4 (375) 5/16 in. HexE3 Phase C 2 --- #6---250 42.4 (375) 5/16 in. HexAC Input To Bypass(Dual Input)E6 Phase A 2 --- #6---250 42.4 (375) 5/16 in. HexE7 Phase B 2 --- #6---250 42.4 (375) 5/16 in. HexE8 Phase C 2 --- #6---250 42.4 (375) 5/16 in. HexSingle-Feed Jumper Busfrom Rectifier InputTerminals to Bypass InputTerminalsRectifier Phase A N/A 12.5 (110) M8 Hex BoltBypass Phase A N/A 22.6 (200) M10 Hex BoltRectifier Phase B N/A 12.5 (110) M8 Hex BoltBypass Phase B N/A 22.6 (200) M10 Hex BoltRectifier Phase C N/A 12.5 (110) M8 Hex BoltBypass Phase C N/A 22.6 (200) M10 Hex BoltAC Output toCritical LoadE9 Phase A 2 --- #6---250 42.4 (375) 5/16 in. HexE10 Phase B 2 --- #6---250 42.4 (375) 5/16 in. HexE11 Phase C 2 --- #6---250 42.4 (375) 5/16 in. HexDC Input fromBattery to UPSE4 Positive 2 --- #2---600 kcmil 56.5 (500) 1/2 in. HexE5 Negative 2 --- #2---600 kcmil 56.5 (500) 1/2 in. HexInput and Output Neutral E12 Neutral 8 --- #6---250 42.4 (375) 5/16 in. HexCustomer Ground Ground Ground 8 --- #14---1/0 5.6 (50) Slotted