INM 725B Rev 2110713 4 24 IEC61850 ServerThe IEC61850 is available on Port 3 and can provide the following data onto the network:• Input Status• Alarm Status• Pushbutton status• Internal Status• Disable StatusThis data will be time stamped to 1ms and will be available via polling or buffered reporting(RCB’s).NOTEEach event type must be enabled via the configuration software to make it available onthe IEC61850 network.The RTK 725B can also be configured to allow for the following to be controlled on theannunciator via IEC61850 using Single point control (SPC):• Inputs• PushbuttonsNOTE:Inputs and pushbuttons must be configured as Remote to be controlled via IEC61850As default the device is loaded a Generic SCL file, which is taken from the ICD file for thedevice. The default IED name will be RTK 725B.As default the following configuration will be provided:BRCB’s• Rep1 - reporting data and quality change of Input dataset• Rep2 - reporting data and quality change of Internal dataset• Rep3 - reporting data and quality change of pushbutton dataset• Rep4 - reporting data and quality change of card_status dataset• Rep5 - reporting data and quality change of alarm datasetNOTE:Event type must be enabled in the configuration software otherwise no data changewill be reportedDatasets• Internal - All internal status inc quality and timestamp• Card_Status - All alarm card status inc quality and timestamp• Pushbuttons - All pushbutton inc quality and timestamp• Input_Status - All input channels status only• Inputs - All input status inc quality and timestamp• Alarms - All alarm status inc quality and timestamp• Disable - All disable status inc quality and timestampNote:If device has more than 100 inputs then these will be spilt across 2 data sets.