58INM 725B Rev 217 INDIVIDUAL CHANNEL REPEAT RELAYSEach four channel alarm card can be supplied with an optional four channel relay card, part noCB6613POP1, which plugs into the four channel alarm card and provides the user with a volt-free contact per alarm channel for use with 3rd Party devices.Each relay is equipped with a C/O contact and the user can select the contact state to N/C orN/O using a 3 way header and 2 way shorting bar located on the card as shown belowWARNING !Remove ALL power from the unit and fully remove the card before changingany jumpersEach relay can be configured in software to operate in accordance with one of the following:-7 1 Input FollowerThe relay changes state each time there is a change to the associated signal input contact.7 2 Logic FollowerThe relay changes state on alarm and remains in the abnormal state until the input hasreturned to normal and the logic has been reset using the pushbuttons associated with the ISAsequence set for this channel.7 3 Display FollowerThe relay changes state on alarm and faithfully follows the display window i.e. Flashing, Steadyor Off depending on the alarm sequence selected for this channel.ORRELAYCONTACTSTATENORMALLYOPENNORL1NCLK1LK2NCNORL2LK3NCRL3NONCNOLK4RL4NORMALLYCLOSEDNCNOLK4LK4SIDE VIEWNONCCB6613POP1REPEAT RELAYCARD