46INM 725B Rev 21The settings are available on the following (4) channel alarm cardsCard Type FeaturesCB6611POP1 24/125V Signal InputCB6611POP3 24/125V Signal Input plus 3 x Pushbutton InputsCB6611POP5 24/125V Signal Input and Time Stamping OptionCB6611POP7 24/125V Signal Input plus 3 x Pushbutton Inputs and Time Stamping OptionDifferential Input VersionsCard Type FeaturesCB6611POP9 24/125V Differential Signal InputsCB6611POP11 24/125V Differential Signal Inputs plus Time Stamping Option5 3 Setting Inputs for use with 48VDCAs an option RTK 725B systems can be supplied with each 4 channel alarm card suitable foruse with 48VDC signal inputs.5 4 Setting Inputs for use with 48VACRTK 725B signal inputs are bi-polar and therefore suitable for use with 48VAC.However when using AC inputs additional filters are added which result in a 25mS responsetime before the alarm activates.In systems using Time Stamping the alarm would still indicate the time the alarm first occurredto the millisecond.To set the signal supply voltage on each input to either 48VDC or 48VAC, a drop-down menu isprovided in the Configuration Software. Selection is made under the Input tab using the drop-down menu labelled “Field Contact Voltage (V)”The settings are available on the following (4) channel alarm cardsCard Type FeaturesCB6611POP2 48V Signal InputCB6611POP4 48V Signal Input plus 3 x Pushbutton InputsCB6611POP6 48V Signal Input and Time Stamping OptionCB6611POP8 48V Signal Input plus 3 x Pushbutton Inputs and Time Stamping OptionDifferential Input VersionsCard Type FeaturesCB6611POP10 48V Differential Signal InputsCB6611POP12 48V Differential Signal Inputs plus Time Stamping Option