12INM 725B Rev 21Full details of programming are provided in later sections of this manual.1 20 CAL ModeWARNING !Installation, configuration and maintenance of this annunciator must onlybe performed by competent service personnelWARNING !Hazardous voltages may be present when pushbutton panel is removed.Take care not to touch any exposed parts on pushbutton panel orannunciator beyond those specified in the instructions below.The RTK 725B unit can be placed into CAL mode which allows the user to view the dynamicstatus of the associated plant inputs or the user can use the pushbutton module to set the nonalarm state of each alarm (N/O or N/C).To place the unit into CAL mode the CAL switch needs to be pushed down in the direction ofthe arrow as indicated above.Whilst in CAL mode the PWR / COM LED bars flash followed by the WD / FC LED bars and thissequence cycles until the cal switch is turned off.Please note whilst in CAL mode the pushbuttons have alternative functions and the CAL switchmust be in the OFF mode for the normal pushbutton functions to operate correctly.If an alarm occurs whilst in CAL mode the audible will sound and once the user places theswitch back to normal the alarm will be displayed in the normal way.Push Downfor CAL Mode