Introduction2 S801+ Soft Starter MN03900002E—November 2012 www.eaton.comStandards and Certifications● UL 508● CSA 22.2-14-1995● IEC 60947-4-2● CCC GB14048CE ConformanceEMC Conformance1. The 24 Vdc power supply must be grounded.2. Add ferrite, Fair-Rite #0446176451 to DC Control PowerLeads and Control I/O Leads (all through one ferrite) atS801+.RF Susceptibility StatementIt is possible, in the presence of strong RF fields, and atspecific RF frequencies, that this device could indicate anincrease of up to 40V in the measured line voltages in the370 to 420 kHz frequency range; or an increase of up to 10%(FLA) of the measured load currents in the 111 to 132 MHzand 152 to 155 MHz frequency range. Should this occur, andaffect the functions of the required motor protectionsettings, refer to the troubleshooting section of this manual.Immunity Severity LevelElectrostatic DischargeIEC 61000-4-24 kV contact discharge8 kV air dischargeElectromagnetic FieldIEC 61000-4-310 V/m80–1000 MHz2 anglesFast Transient BurstsIEC 61000-4-42 kV, 5 kHz rep, 2 min. intervals1.2/50 uS to 8/20 uS SurgesIEC61000-4-52 kV Line to earth1 kV Line to Line1 minute intervalsConducted RFIEC 61000-4-610 V rms0.15 to 80 MHz50 Hz Magnetic FieldIEC 61000-4-8N/AVoltage dipsInterruptIEC 61000-4-1130% dip at 10 mS60% dip at 100 mS100% dip at 5 SEmissionsRadiated EN 55011, Class AConducted EN 55011, Class A