S801+ Operating ConfigurationS801+ Soft Starter MN03900002E—November 2012 www.eaton.com 27Initial Configuration:1. It is suggested that the S801+ Soft Starter be configuredbefore applying the line voltage. Before applying the Linevoltage, apply 24 Vdc to the Supply connections of theS801+’s control terminal block.2. Set the Operating Parameters to the desired values.These settings assume the motor has a 1.15 ServiceFactor.Operating Parameters—Soft Start Configuration—S801+ …N3S StandardSoft Start ConfigLine Connected Motor Units Minimum Maximum Default NotesOverld Trip FLAS801+N37… Amps 11 37 11 Motor FLA parameter must be set to motornameplate FLA to achieve proper overloadprotectionS801+N66… Amps 20 66 20S801+R10… Amps 32 105 32S801+R13… Amps 42 135 42S801+T18… Amps 56 180 56S801+T24… Amps 75 240 75S801+T30… Amps 95 304 95S801+U36… Amps 112 360 112S801+U42… Amps 131 420 131S801+U50… Amps 156 500 156S801+V36… Amps 112 360 112S801+V42… Amps 131 420 131S801+V50… Amps 156 500 156S801+V65… Amps 203 650 203S801+V72… Amps 225 720 225S801+V85… Amps 265 850 265S801+V10… Amps 312 1000 312Overload On Disable OnJam On Disable OnStall On Disable OnPhase Loss On Disable OnPhase Reversal On Disable OnReset Mode Manual Auto ManualRamp Start/Current Limit Ramp Current RampKick Start Torque % 0 85 0Kick Start Time Seconds 0 2 0Initial Torque % 0 85 45Ramp Time Seconds 0.5 180 20Ovrld Trip Class 5 30 20Soft Stop Time Seconds 0 60 0