InstallationS801+ Soft Starter MN03900002E—November 2012 www.eaton.com 17Basic Connection Diagram for 2-Wire PushbuttonNotes1. A minimum wire of 14 AWG (2.5 mm2 ) should be usedbetween the control power supply and the controlterminal block.2. See Using an Auxiliary Relay section below if it is desiredto use a relay instead of an indicating lamp for terminals13, 14, 95, 96 and 98.3. 120 Vac may be applied to terminals 13, 14, 95, 96,and 98.4. Add ferrite, Fair-Rite #0446176451 to DC Power Leadsand Control I/O Leads (all through one ferrite) at S801+.5. Auxiliary relays: 3 amps at 120 Vac or 24 Vdc, 10 ampsmax. (resistive) switching.E-Stop(+) Us 24 Vdc (-) UsResetLocalStart/RunMaintainedMomentaryFerriteAux Relays-24V+24VPermissiveStartJogDisable OvldReset98969514134321P+-