xComfort Room Controller Touch User Manual 1v00_EN 11 | P a g e2.7 Edit Operating Instructions2.7.1 Change Pre-Defined Set-Point TemperatureThe Room Controller Touch supports up to 2 x 4 (4 for heating and 4 for cooling) different pre-definedset-point temperatures (operation modes) which can be manually (re-)programmed via the screen.Frost protection mode. Factory default values 10°C/32°C (or -5K with Room Manager)Standby or Night mode. Factory default values 18°C/28°C (or -0,5K with Room Manager)Economy mode. Factory default values 19°C/26°C (or -1K with Room Manager)Comfort or Day mode. Factory default value 21°C/24°C (or 0K with Room Manager)Sensor modeWhen connected to the xComfort SHC, the values of the pre-defined temperature are the same as theset-point temperatures in the SHC. Making a manual change on the Room Controller Touch will alsochange the set-point in the SHC (and v.v.).When connected to a Room Manager, the predefined temperatures are used as offset in the RoomManager for the Room Manager’s current set-point temperature.Control modeThe initial values used in controller mode are programmed during the installation (MRF). The set-pointvalues are used by the Room Controller Touch for the climate control.Note: If the ‘Heating&Cooling’ mode is active, the Room Controller will maintain a minimumtemperature difference between the heating set-point and cooling set-point temperature(dead zone) to prevent the continuous switching between heating and cooling. This deadzone value can be configured during installation. The factory default is 3K.OptionalStep 1