• Initialization of the adjustable frequency drive torestore factory default settings does not changedata stored in the keypad memoryWARNINGUNINTENDED START!When the adjustable frequency drive is connected to ACline power, the motor may start at any time. Theadjustable frequency drive, motor, and any drivenequipment must be in operational readiness. Failure to bein operational readiness when the adjustable frequencydrive is connected to AC line power could result in death,serious injury, or equipment or property damage.4.2.1 Uploading Data to the Keypad1. Press [Off] to stop the motor before uploading ordownloading data.2. Go to K-50 Keypad Copy.3. Press [OK].4. Select All to keypad.5. Press [OK]. A progress bar shows the uploadingprocess.6. Press [Hand] or [Auto] to return to normaloperation.4.2.2 Downloading Data from the Keypad1. Press [Off] to stop the motor before uploading ordownloading data.2. Go to K-50 Keypad Copy.3. Press [OK].4. Select All from keypad.5. Press [OK]. A progress bar shows thedownloading process.6. Press [Hand] or [Auto] to return to normaloperation.4.3 Restoring Default SettingsCAUTIONInitialization restores the unit to factory default settings.Any programming, motor data, localization, andmonitoring records will be lost. Uploading data to thekeypad provides a backup before initialization.Restoring the adjustable frequency drive parametersettings back to default values is done by initialization ofthe adjustable frequency drive. Initialization can bethrough H-03 Restore Factory Settings or manually.• Initialization using H-03 Restore Factory Settingsdoes not change adjustable frequency drive datasuch as operating hours, serial communicationselections, personal menu settings, fault log,alarm log, and other monitoring functions• Using H-03 Restore Factory Settings is generallyrecommended.• Manual initialization erases all motor,programming, localization, and monitoring dataand restores factory default settings.4.3.1 Recommended Initialization1. Press [Main Menu] twice to access parameters.2. Scroll to H-03 Restore Factory Settings.3. Press [OK].4. Scroll to [2] Restore Factory Settings.5. Press [OK].6. Remove power to the unit and wait for thedisplay to turn off.7. Apply power to the unit.Default parameter settings are restored during start-up.This may take slightly longer than normal.8. Alarm 80 is displayed.9. Press [Reset] to return to operation mode.4.3.2 Manual Initialization1. Remove power to the unit and wait for thedisplay to turn off.2. Press and hold [Status], [Main Menu], and [OK] atthe same time and apply power to the unit.Factory default parameter settings are restored duringstartup. This may take slightly longer than normal.Manual initialization does not the following adjustablefrequency drive information.• ID-00 Operating Hours• ID-03 Power Up's• ID-04 Over Temp's• ID-05 Over Volt'sUser Interface AF-600 FP Design and Installation Guide4-4 DET-768A44