Symptom Possible Cause Test SolutionMotor not runningService switch open or missingmotor connectionCheck if the motor is connectedand the connection is notinterrupted (by a service switch orother device).Connect the motor and check theservice switch.No line power with 24 V DCoption cardIf the display is functioning but nooutput, check that line power isapplied to the adjustable frequencydrive.Apply line power to run the unit.keypad Stop Check if [Off] has been pressed. Press [Auto] or [Hand] (dependingon operation mode) to run themotor.Missing start signal (Standby) Check E-01 Terminal 18 Digital Inputfor correct setting for terminal 18(use default setting).Apply a valid start signal to startthe motor.Motor coast signal active(Coasting)Check if a coast inv command isprogrammed for the terminal inparameter group E-0# DigitalInputsApply 24 V on terminal or programthis terminal to No operation.Wrong reference signal source Check reference signal: Local,remote or bus reference? Presetreference active? Terminalconnection correct? Scaling ofterminals correct? Reference signalavailable?Program correct settings. CheckF-02 Operation Method. Set presetreference active in parameterC-05 Multi-step Frequency 1 - 8 .Check for correct wiring. Checkscaling of terminals. Checkreference signal.Motor running in wrongdirectionMotor rotation limit Check that H-08 Reverse Lock isprogrammed correctly.Program correct settings.Active reversing signal Check if a reversing command isprogrammed for the terminal inparameter group E-0# Digital inputs.Deactivate reversing signal.Wrong motor phase connection See 3.5 Check Motor Rotation in thismanual.Motor is not reachingmaximum speedFrequency limits set wrong Check output limits in F-17 MotorSpeed High Limit [RPM], F-15 MotorSpeed High Limit [Hz] and F-03 MaxOutput Frequency 1Program correct limits.Reference input signal not scaledcorrectlyCheck reference input signalscaling in AN-## Reference limits inparameter group F-5#.Program correct settings.Motor speed unstablePossible incorrect parametersettingsCheck the settings of all motorparameters, including all motorcompensation settings. For closed-loop operation, check PID settings.Check settings in parameter groupAN-##. For closed-loop operation,check settings in parameter groupCL-0#Motor runs roughPossible over-magnetization Check for incorrect motor settingsin all motor parameters.Check motor settings in parametergroups P-0# Motor Data, P-3# AdvMotor Data, and H-5# Load Indep.Setting.Motor will not brakePossible incorrect settings in thebrake parameters. Possible tooshort ramp-down times.Check brake parameters. Checkramp time settings.Check parameter group B-0# DCbrake and F-5# Extended Reference.Basic Troubleshooting AF-600 FP Design and Installation Guide10-2 DET-768A100