CHAPTER 5: SETTINGS PRODUCT SETUPD60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 5-215Session settingsSETTINGS PRODUCT SETUP SECURITY SESSION SETTINGSSESSION LOCKOUT — This setting specifies the number of failed authentications before the device blocks subsequentauthentication attempts for the lockout period. A value of zero means lockout is disabled.SESSION LOCKOUT PERIOD — This setting specifies the period of time in minutes of a lockout period. A value of 0 means thatthere is no lockout period.Restore defaultsSETTINGS PRODUCT SETUP SECURITY RESTORE DEFAULTSLOAD FACTORY DEFAULTS — This setting is used to reset all the settings, communication, and security passwords. AnAdministrator role is used to change this setting and a Supervisor role (if not disabled) approves it.SupervisorySETTINGS PRODUCT SETUP SECURITY SUPERVISORYThe Supervisory menu settings are available for Supervisor role only, or if the Supervisor role is disabled then for theAdministrator role only.In Device authentication mode, the Observer role does not have a password associated with it. In Serverauthentication mode the Observer role requires a password.If you are locked out of the software, contact GE Grid Solutions for the default password. When using CyberSentry,the default password is "ChangeMe1#".Once the passwords are set, the Administrator with Supervisor approval can change the role-associated password.In CyberSentry, password encryption is not supported. SESSION SETTINGS SESSION LOCKOUT:3Range: 0 to 99 SESSION LOCKOUTPERIOD: 3 minRange: 0 to 9999 minutes RESTORE DEFAULTS LOAD FACTORYDEFAULTS: NoRange: Yes, No SUPERVISORY DEVICEAUTHENTICATION: YesRange: Yes, No BYPASS ACCESS:DisabledRange: Local, Remote, Local and Remote, Disabled,Pushbuttons LOCK RELAY:DisabledRange: Enabled, Disabled FACTORY SERVICEMODE: DisabledRange: Enabled, Disabled SELF TESTSSee below SUPERVISOR ROLE:DisabledRange: Enabled, Disabled SERIAL INACTIVITYTIMEOUT: 1 minRange: 1 to 9999 minutes