CHAPTER 5: SETTINGS PRODUCT SETUPD60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 5-895The binary input points are mapped using elements from a list of possible FlexLogic operands. A maximum of 96 binaryinputs (points) can be mapped this way.The IEC 60870-5-103 point list always starts with point 0 and ends at the first "Off" value. Since the IEC 60870-5-103 pointlist must be in a continuous block, any points assigned after the first "Off" point are ignored.For each defined point, set appropriate values for the Function Type (FUN) and Information Number (INF), which form theInformation Object Identifier field of the ASDU, as defined in IEC 60870-5-103.The binary input points are sent as Class 1 data. They are sent either as a response to a general interrogation receivedfrom the controller or reported spontaneously. Spontaneous transmission occurs as a response to cyclic Class 2 requests.If the D60 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in thecontrol field of the response).SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 60870-5-103 IEC103 INPUTS MEASURANDS POINT 1See below POINT 95See below POINT 0 POINT 0 FUN0Range: 0 to 255 in steps of 1 POINT 0 INF0Range: 0 to 255 in steps of 1 POINT 0 InputOffRange: FlexLogic operand POINT 95 POINT 95 FUN0Range: 0 to 255 in steps of 1 POINT 95 INF0Range: 0 to 255 in steps of 1 POINT 95 InputOffRange: FlexLogic operand IEC103 INPUTS MEASURANDS ASDU 1See below ASDU 4 ASDU 1 ASDU 1 TYP:9Range: 3 or 9 ASDU 1 FUN:0Range: 0 to 255 in steps of 1 ASDU 1 INF:0Range: 0 to 255 in steps of 1 ASDU 1 SCAN TOUT:0Range: 0 to 1000 s in steps of 1