CHAPTER 5: SETTINGS PRODUCT SETUPD60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL 5-595RxGOOSE1 Dst MACRange: any 12 digit hexadecimal numberDefault: 01-0C-CD-01-00-00When the RxGOOSE1 MODE setting is R-GOOSE, the value of this setting is not used, the destination Media AccessControl (MAC) address for RxGOOSE1 messages is calculated based on the RxGOOSE DST IP address. Otherwise, set thissetting to the MAC address of the publisher. Only received GOOSE messages having a MAC address equal to this valueare accepted as valid RxGOOSE1 messages. An entered address of zero disables RxGOOSE1.If the publisher is a UR series 7.3x device, the setting needs to match the value of the publisher’s TxGOOSE DST MACsetting.RxGOOSE1 ETYPE APPIDRange: 0 to 65535 in steps of 1Default: 0If the value entered is non-zero, the APPID field of incoming GOOSE messages must exactly match this value for themessage to be accepted as a valid RxGOOSE1 message. If the value entered is zero, RxGOOSE1 does not check the valuereceived in the APPID field.If the publisher is a UR series 7.3x device, the setting needs to match the value of the publisher’s TxGOOSE ETYPE APPIDsetting.RxGOOSE1 GoCBRefRange: 0 to 129 alphanumeric, underscore, slash and period characters, beginning with an alpha characterDefault: empty stringThe gocbRef field of incoming GOOSE messages must match this value for the message to be accepted as a validRxGOOSE1 message. If the entered value is the empty string, RxGOOSE1 is disabled. If not the empty string, the entryneeds to be an ACSI ObjectReference to the publishing control block in the format:/LLN0.where is the function-related name if the logical device containing the publishing control block has "ldName"configured, otherwise the product-related name of that logical device, and is the name of the publishingcontrol block.The D60 translates the ACSI format required for this setting to the MMS format used in GOOSE messages:/LLN0$GO$If the publisher is a UR 7.3x or 7.40 series device, is the value of the publisher's Master functional ldNamesetting if that setting is not empty, otherwise it is the value of the publisher's IED NAME suffixed with "Master". If thepublisher is a UR 7.3x series device, is "GoCB" suffixed with the two digit TxGOOSE instance number, forexample "GoCB01". If the publisher is a UR 7.40 series device, is as specified earlier in the TxGOOSEsection of this chapter.RxGOOSE1 datSetRange: 0 to 32 alphanumeric and underscore characters, beginning with an alpha characterDefault: empty stringIf the entered value has one or more characters, the datSet field of incoming GOOSE messages must exactly match thisvalue prefixed by /LLN0$ for the message to be accepted as a valid RxGOOSE1 message. is asspecified in the RxGOOSE GoCBRef setting above. If the entered value is the empty string, RxGOOSE1 does not check thevalue received in the datSet field.If the publisher is a UR 7.3x series device, set this setting to the value of the publisher's DataSetxx name setting, where xxis the instance number of the data set selected by the publisher's TxGOOSE datSet setting. If the publisher is a UR 7.40series device, datSet is as specified in the DataSets section of this chapter.RxGOOSE1 ConfRevRange: 0 to 4294967295 in steps of 1Default: 1If the value entered is non-zero, the confRev field of incoming GOOSE messages must exactly match this value for themessage to be accepted as a valid RxGOOSE1 message. If the entered value is zero, RxGOOSE1 does not check the valuereceived in the confRev field.