CHAPTER 4: INTERFACES FLEXLOGIC DESIGN AND MONITORING USING ENGINEERL30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 4-394Some information displayed in the compile messages updates automatically, for example messages after a device isunplugged.Figure 4-40: Compile and check the logic12. View the FlexLogic equations by navigating in the Offline Window area to FlexLogic > FlexLogic Equation Editor. Thewindow opens with the entries displayed in the next tab.Figure 4-41: Logic displayed in FlexLogic Equation Editor13. Save the work.The logic diagram has been created and the FlexLogic equations populated. The next steps are to upload the file to thedevice and to monitor the device.4.4.1.4 Compiled results and warning messagesWhen a yellow caution icon displays in the Offline Window area, it means that the settings file is not synchronized with theonline device. Right-click the device in the Offline Window area, and select the Update SCL files option. SCL refers to theSubstation Configuration Language. An Instantiated IED capability description (IID) file is an example of an SCL file andcontains the actual settings on a UR device.Figure 4-42: Settings files not synchronized between offline and online filesWhen the Update SCL files option is selected, the CID and IID files in the device folder are updated by the userconfiguration in the IEC 61850 panel and thereby become synchronized. The CID file and the IID file (depending on thepreference 'Do not update IID file when updating SCL files') are updated. If the CID file is not already there, it is generated.The location of these files is C:\ProgramData\GE Power Management\urpc, for example, in the Offline and Online folders.Any FlexLogic equations entered in the Offline Window area are erased. The logic drawn in the Logic Designer window inEngineer in the Offline Window area remain. The warning icon disappears after updating.