5-202 L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUALGROUPED ELEMENTS CHAPTER 5: SETTINGS5Figure 5-98: Phase time overcurrent 1 logic5.7.4.4 Phase instantaneous overcurrent (ANSI 50P, IEC PIOC)SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) PHASE CURRENT PHASE IOC 1(4) PHASE IOC 1 PHASE IOC1FUNCTION: DisabledRange: Disabled, Enabled PHASE IOC1 SIGNALSOURCE: SRC 1Range: SRC 1, SRC 2 PHASE IOC1PICKUP: 1.000 puRange: 0.020 to 30.000 pu in steps of 0.001 PHASE IOC1 PICKUPDELAY: 0.00 sRange: 0.00 to 600.00 s in steps of 0.01 PHASE IOC1 RESETDELAY: 0.00 sRange: 0.00 to 600.00 s in steps of 0.01 PHASE IOC1 BLOCK A:OffRange: FlexLogic operand PHASE IOC1 BLOCK C:OffRange: FlexLogic operand PHASE IOC1TARGET: Self-resetRange: Self-reset, Latched, Disabled PHASE IOC1EVENTS: DisabledRange: Disabled, Enabled