5-44 L60 Line Phase Comparison Relay GE Multilin5.3 SYSTEM SETUP 5 SETTINGS5b) VOLTAGE BANKSPATH: SETTINGS ÖØ SYSTEM SETUP Ö AC INPUTS ÖØ VOLTAGE BANK F5One bank of phase/auxiliary VTs can be set, where voltage banks are denoted in the following format (X represents themodule slot position letter):Xa, where X = {F} and a = {5}.See the Introduction to AC Sources section at the beginning of this chapter for additional details.With VTs installed, the relay can perform voltage measurements as well as power calculations. Enter the PHASE VT F5 CON-NECTION made to the system as “Wye” or “Delta”. An open-delta source VT connection would be entered as “Delta”. Seethe Typical Wiring Diagram in Chapter 3 for details.The nominal PHASE VT F5 SECONDARY voltage setting is the voltage across the relay input terminals when nominalvoltage is applied to the VT primary.For example, on a system with a 13.8 kV nominal primary voltage and with a 14400:120 volt VT in a Delta connec-tion, the secondary voltage would be 115, i.e. (13800 / 14400) × 120. For a Wye connection, the voltage valueentered must be the phase to neutral voltage which would be 115 / = 66.4.On a 14.4 kV system with a Delta connection and a VT primary to secondary turns ratio of 14400:120, the voltagevalue entered would be 120, i.e. 14400 / 120. VOLTAGE BANK F5PHASE VT F5CONNECTION: WyeRange: Wye, DeltaMESSAGE PHASE VT F5SECONDARY: 66.4 VRange: 50.0 to 240.0 V in steps of 0.1MESSAGE PHASE VT F5RATIO: 1.00 :1Range: 1.00 to 24000.00 in steps of 0.01MESSAGE AUXILIARY VT F5CONNECTION: VagRange: Vn, Vag, Vbg, Vcg, Vab, Vbc, VcaMESSAGE AUXILIARY VT F5SECONDARY: 66.4 VRange: 50.0 to 240.0 V in steps of 0.1MESSAGE AUXILIARY VT F5RATIO: 1.00 :1Range: 1.00 to 24000.00 in steps of 0.01NOTE3