GE Multilin L60 Line Phase Comparison Relay 5-1535 SETTINGS 5.5 GROUPED ELEMENTS5c) PHASE OVERVOLTAGE (ANSI 59P)PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) ÖØ VOLTAGE ELEMENTS ÖØ PHASE OVERVOLTAGE1The phase overvoltage element may be used as an instantaneous element with no intentional time delay or as a DefiniteTime element. The input voltage is the phase-to-phase voltage, either measured directly from Delta-connected VTs or ascalculated from phase-to-ground (Wye) connected VTs. The specific voltages to be used for each phase are shown below.Figure 5–90: PHASE OVERVOLTAGE SCHEME LOGIC PHASE OVERVOLTAGE1PHASE OV1FUNCTION: DisabledRange: Disabled, EnabledMESSAGE PHASE OV1 SIGNALSOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4MESSAGE PHASE OV1PICKUP: 1.000 puRange: 0.000 to 3.000 pu in steps of 0.001MESSAGE PHASE OV1 PICKUPDELAY: 1.00 sRange: 0.00 to 600.00 s in steps of 0.01MESSAGE PHASE OV1 RESETDELAY: 1.00 sRange: 0.00 to 600.00 s in steps of 0.01MESSAGE PHASE OV1 BLOCK:OffRange: FlexLogic™ OperandMESSAGE PHASE OV1TARGET: Self-resetRange: Self-reset, Latched, DisabledMESSAGE PHASE OV1EVENTS: DisabledRange: Disabled, EnabledPHASE OV1FUNCTION:PHASE OV1BLOCK:PHASE OV1 SOURCE:PHASE OV1PICKUP:PHASE OV1CURVE:PHASE OV1DELAY:Disabled = 0Off = 0Source VT = DeltaSource VT = WyeEnabled = 1VAB}VBCVCAPHASE OV1 A PKPPHASE OV1 B PKPPHASE OV1 C PKPPHASE OV1 PKPPHASE OV1 A DPOPHASE OV1 B DPOPHASE OV1 C DPOPHASE OV1 A OPPHASE OV1 B OPPHASE OV1 C OPPHASE OV1 OPANDSETTINGSETTINGSETTINGSETTINGFLEXLOGIC OPERANDSFLEXLOGIC OPERANDFLEXLOGIC OPERAND827066A5.CDRPHASE OV1 MODE:Phaseto PhaseVAGVBGVCGPhaseto GroundVABVBCVCASETTINGtttVVVRUN VAG or VAB PICKUP<RUN VBG or VBC PICKUP<RUN VCG or VCA PICKUP<ORORPHASE OV1 DPOFLEXLOGIC OPERANDAND