5-234 L60 Line Phase Comparison System GE Multilin5.6 CONTROL ELEMENTS 5 SETTINGS55.6.5 TRIP OUTPUTPATH: SETTINGS CONTROL ELEMENTS TRIP OUTPUT TRIP OUTPUTTRIP MODE:DisabledRange: Disabled, 3 Pole Only, 3 Pole & 1 PoleMESSAGE TRIP 3-POLE INPUT-1:OffRange: FlexLogic operandMESSAGE TRIP 3-POLE INPUT-2:OffRange: FlexLogic operand↓MESSAGE TRIP 3-POLE INPUT-6:OffRange: FlexLogic operandMESSAGE TRIP 1-POLE INPUT-1:OffRange: FlexLogic operandMESSAGE TRIP 1-POLE INPUT-2:OffRange: FlexLogic operand↓MESSAGE TRIP 1-POLE INPUT-6:OffRange: FlexLogic operandMESSAGE TRIP RECLOSE INPUT-1:OffRange: FlexLogic operandMESSAGE TRIP RECLOSE INPUT-2:OffRange: FlexLogic operand↓MESSAGE TRIP RECLOSE INPUT-6:OffRange: FlexLogic operandMESSAGE TRIP SEAL-IN DELAY:0.000 sRange: 0 to 65.535 s in steps of 0.001MESSAGE TRIP RESET:CBaux OR CustomRange: Pole Curr OR Custom, CBaux OR Custom,CustomMESSAGE START TMR Z2PH Inp1:OffRange: FlexLogic operandMESSAGE START TMR Z2PH Inp2:OffRange: FlexLogic operandMESSAGE START TMR Z2GR Inp1:OffRange: FlexLogic operandMESSAGE START TMR Z2GR Inp2:OffRange: FlexLogic operandMESSAGE TRIP FORCE 3-POLE:OffRange: FlexLogic operandMESSAGE TRIP PILOT PRIORITY:0.000 sRange: 0 to 65.535 s in steps of 0.001MESSAGE REVERSE FAULT:OffRange: FlexLogic operand