CHAPTER 5: SETTINGS PRODUCT SETUPL90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-635Figure 5-21: RxGOOSE Boolean panelMost of the settings are configured by drag-and-drop. However the ID, DEFAULT STATE, and EVENTS settings must beindividually entered when the factory default values are not acceptable.RxGOOSE Boolean1 IDRange: 0 to 20 charactersDefault: RxG Bool1This setting allows the user to assign descriptive text to the name of the RxGOOSE Boolean1 FlexLogic operand. The fulloperand name is the value of this setting appended with " On". The standard and enhanced front panels display the first17 characters of this setting plus " On" to fit the 20 character display.RxGOOSE Boolean1 RxGOOSERange: None, RxGOOSE1, RxGOOSE2, and so onDefault: NoneThis setting selects the RxGOOSE containing the value that drives the RxGOOSE Boolean1 FlexLogic operand. If set toNone, the RxGOOSE Boolean1 FlexLogic operand assumes its default state.RxGOOSE Boolean1 MemberRange: 1 to 64 in steps of 1Default: 1This setting selects the GOOSE message member that drives the RxGOOSE Boolean1 FlexLogic operand. A setting of 1selects the first member, 2 selects the second member, and so on. Entering a number greater than the number ofmembers in the message and entering the number of a member which does not contain a BOOLEAN results in theRxGOOSE Boolean1 FlexLogic operand assuming its default state. The Subscribed to column identifies the particularBoolean subscribed to even if the member is a structure containing more than one Boolean.RxGOOSE Boolean1 DEFAULT STATERange: On, Off, Latest/On, Latest/OffDefault: OffThis setting selects the logic state for the RxGOOSE Boolean1 FlexLogic operand if the UR has just completed startup andthe selected RxGOOSE has not yet received a message, or the selected RxGOOSE has lost its connectivity with thepublisher. The following choices are available: