CHAPTER 5: SETTINGS PRODUCT SETUPL90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-675in the integer result. The FlexElement Base Units table in the Settings > FlexLogic > FlexElements section later, whichtabulates the per-unit base value used by its pickup setting and implies the per-unit base used by other FlexAnalogs, canbe of use in selecting a value for the RxGOOSE Analog1 PU setting.Some UR elements have requirements for the type of input operands, for instance current type or voltage type. Theseelements assume that RxGOOSE Analog operands are of whatever type is necessary to meet these requirements.The per-unit base setting represents thousands, not single units. For example, a PU base of 1.000 is actually 1000 and aPU base of 0.001 is 1.When using RxGOOSE Analogs and PU base in FlexElements, the largest value that can be displayed in the FlexElementactual values is 2,140,000.000.ReportsNavigate to Settings > Product Setup > Communications > IEC 61850 > Reports.Report settingsNavigate to Settings > Product Setup > Communications > IEC 61850 > Reports > Report Settings.ReportSettings rptIDRange: Dyn, ConfDefault: DynWhen set to Dyn, the RptID attribute in any buffered and unbuffered report control block can be modified by an MMSclient while the control block's RptEna attribute is false. The RptID is the name of the report.ReportSettings optFieldsRange: Dyn, ConfDefault: DynWhen set to Dyn, the OptFlds attribute in any buffered and unbuffered report control block can be modified by an MMSclient while the control block's RptEna attribute is false.ReportSettings bufTimeRange: Dyn, ConfDefault: DynWhen set to Dyn, the BufTm attribute in any buffered and unbuffered report control block can be modified by an MMSclient while the control block's RptEna attribute is false.ReportSettings trgOpsRange: Dyn, ConfDefault: DynWhen set to Dyn, the TrgOps attribute in any buffered and unbuffered report control block can be modified by an MMSclient while the control block's RptEna attribute is false.ReportSettings intgPdRange: Dyn, ConfDefault: DynWhen set to Dyn, the IntgPd attribute in any buffered and unbuffered report control block can be modified by an MMSclient while the control block's RptEna attribute is false.Buffered and unbuffered reportsNavigate to Settings > Product Setup > Communications > IEC 61850 > Reports > Buffered Reports or UnbufferedReports.