6-6 L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUALSTATUS CHAPTER 6: ACTUAL VALUES6The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contactoutput. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line ofthe display indicates the logic state of the contact output.For form-A contact outputs, the state of the voltage and current detectors is displayed as Off, VOff, IOff, On, IOn, and VOn.For form-C contact outputs, the state is displayed as Off or On.6.3.7 Virtual outputsACTUAL VALUES STATUS VIRTUAL OUTPUTSThe present state of up to 96 virtual outputs is shown here. The first line of a message display indicates the ID of the virtualoutput. For example, ‘Virt Op 1’ refers to the virtual output in terms of the default name-array index. The second line of thedisplay indicates the logic state of the virtual output, as calculated by the FlexLogic equation for that output.6.3.8 RxGOOSE statusACTUAL VALUES STATUS RxGOOSE STATUSThe All RxGOOSE Online actual value does not consider RxGOOSE that are not configured or are not used by any RxGOOSEInput.6.3.9 RxGOOSE statisticsACTUAL VALUES STATUS RxGOOSE STATISTICS RxGOOSE 1(64) Cont Op xxOffRange: On, Off, VOff, VOn, IOn, IOff VIRTUAL OUTPUTS Virt Op 1OffRange: On, Off Virt Op 96OffRange: On, Off RxGOOSE STATUS All RxGOOSE Online:YesRange: Yes, No RxGOOSE 1 Status:OfflineRange: Online, Offline RxGOOSE 64 Status:OfflineRange: Online, OfflineThe L90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the timeof ordering. See the Order Codes section of chapter 2 for details. RxGOOSE 1 RxGOOSE 1stNum: 0Range: 0 up to 4,294,967,295 RxGOOSE 1sqNum: 0Range: 0 up to 4,294,967,295The L90 is provided with optional IEC 61850 capability. This feature is specified as a software option at the timeof ordering. See the Order Codes section of chapter 2 for details.