5-44 M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5Figure 5-15: Multiple LANS, no redundancy5.3.5.4 NetworkAs outlined in the previous section, when using more than one Ethernet port, configure each to belong to a differentnetwork or subnet using the IP addresses and mask. Configure the network IP and subnet settings before configuring therouting settings.To obtain a list of all port numbers used, for example for audit purposes, contact GE technical support with substantiatinginformation, such as the serial number and order code of your device.SETTINGS PRODUCT SETUP COMMUNICATIONS NETWORK 1(3) NETWORK PORT 1 PRT1 IP ADDRESS:127.0.0.1Range: standard IPV4 address format PRT1 SUBNET IP MASK:255.0.0.0Range: standard IPV4 address format PRT1 FUNCTION:EnabledRange: Enabled, Disabled NETWORK PORT 2 PRT2 IP ADDRESS:127.0.0.1Range: standard IPV4 address format PRT2 SUBNET IP MASK:255.0.0.0Range: standard IPV4 address format PRT2 REDUNDANCY:NoneRange: None, Failover, PRPRange if no PRP license: None, Failover PRP MCST ADDR:01154E000100Range: 01-15-4E-00-01-00 to 01-15-4E-00-01-FF PRT2 FUNCTION:EnabledRange: Enabled, Disabled NETWORK PORT 3 PRT3 IP ADDRESS:127.0.0.1Range: standard IPV4 address format