5-296 M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUALCONTROL ELEMENTS CHAPTER 5: SETTINGS5REDUCED VOLT TIMER — This setting specifies the time-out value of the transition timer used in the selected transition mode.Figure 5-167: Reduced voltage starting logic5.8.9 Digital elementsSETTINGS CONTROL ELEMENTS DIGITAL ELEMENTS DIGITAL ELEMENT 1(48) DIGITAL ELEMENT 1 DIGITAL ELEMENT 1FUNCTION: DisabledRange: Disabled, Enabled DIG ELEM 1 NAME:Dig Element 1Range: up to 16 alphanumeric characters DIG ELEM 1 INPUT:OffRange: FlexLogic operand DIG ELEM 1 PICKUPDELAY: 0.000 sRange: 0.000 to 999999.999 s in steps of 0.001 DIG ELEM 1 RESETDELAY: 0.000 sRange: 0.000 to 999999.999 s in steps of 0.001 DIGITAL ELEMENT 1PICKUP LED: EnabledRange: Disabled, Enabled DIG ELEM 1 BLOCK:OffRange: FlexLogic operand DIGITAL ELEMENT 1TARGET: Self-resetRange: Self-reset, Latched, Disabled DIGITAL ELEMENT 1EVENTS: DisabledRange: Disabled, EnabledDigital elements run once per power system cycle.As such they can easily fail to react to an input signal or a block signal with a duration less than one power systemcycle. This also means that digital element output can react up to one power system cycle later than the pickupand reset delay settings indicate.Do not use digital elements with transient signals, such as communications commands. Do not use digitalelements where random delays of up to one cycle cannot be tolerated, such as in high speed protection.