Masoneilan SVI II ESD Installation and Maintenance Manual =| 105© 2016 General Electric Company. All rights reserved.Calibration MenuThe Calibration menu shown in Figure 64 provides access to all of the calibration functions forSVI II ESD. If a change is made in the Air-To-Open/Air-To-Close configuration option, or if youmove SVI II ESD to a different valve, or make any change to the valve position linkage, youmust run the find STOPS calibration again.Figure 64 CALIBration MenuSETUP+ + +CALIBration MenuSTOPS**RUNNINGSTOP OP*TUNE***FAILURESTEP 1/3STEP 2/3+/-*CALIB* - ++/-**STEP 3/3If a calibration tuning error occursFAILURE message appears. Press * briefly andautomatically return to TUNE starting point.FAILUREIf a calibration stops error occursFAILURE message appears. Press * briefly andautomatically return to STOPS starting point.+*CALIBCAUTION: These functions stroke the valve over its full range.Do not perform while the valve is controlling the process.TUNE OKSee Figure 62 onpage 102 for full menu