© 2016 General Electric Company. All rights reserved.88 | =GE Oil & GasConfigurationTo perform configuration and calibration you can use either pushbutton display, HART ®handheld communicator, HART® Host with the DD loaded, or ValVue ESD software. Refer to“Pushbuttons and Local Display” on page 98 or the SVI II ESD Help for instructions.The following section describes configuration and calibration procedure using optional localdisplay and pushbuttons.WARNING These procedures can cause the valve to move. Before proceedingbe sure that the valve is isolated from the process. Keep handsclear from moving parts.Configuration with Pushbutton DisplayTo change the current configuration parameters:1. After power up, if SVI II ESD is not in NORMAL mode, switch to NORMAL mode. The displayalternates between POS and SIGNAL indicating NORMAL mode.2. Press + to until MANUAL appears.3. Press * to select MANUAL mode. The display alternates between POS –M and SIGindicating MANUAL mode.4. Press * and SETUP appears.5. Press * again andCONFIG appears.6. Press * to access CONFIGuration menu.7. Set the configuration parameters: Air Action, Air Pressure Units and Language by:a. Pressing * to access and change the parameter.b. Pressing + to move to the next parameter.8. Press + to return to SETUP.9. Press + to return to NORMAL mode.