Menu Text Col Row Default Setting Available OptionsDescriptionI>1 Function 36 21 IEC S Inverse0 = Disabled1 = DT (DT)2 = IEC S Inverse (TMS)3 = IEC V Inverse (TMS)4 = IEC E Inverse (TMS)5 = UK LT Inverse (TMS)6 = Rectifier (TMS)7 = RI (K)8 = IEEE M Inverse (TD)9 = IEEE V Inverse (TD)10 = IEEE E Inverse (TD)11 = US Inverse (TD)12 = US ST Inverse (TD)This setting determines the tripping characteristic for the first stage overcurrent element.I>1 Current Set 36 23 1.0*I8 From 0.08*I8 to 4.0*I8 step 0.01*I8This sets the pick-up threshold for the first stage overcurrent element.I>1 Time Delay 36 24 1 From 0 to 100 step 0.01This sets the DT time delay for the first stage overcurrent element.I>1 TMS 36 25 1 From 0.025 to 1.2 step 0.025This is the Time Multiplier Setting to adjust the operate time of IEC IDMT curves.I>1 Time Dial 36 26 1 From 0.01 to 100 step 0.01This is the Time Multiplier Setting to adjust the operate time of IEEE/US IDMT curves.I>1 K (RI) 36 27 1 From 0.1 to 10 step 0.05This setting defines the TMS constant to adjust the operate time of the RI curve.I>1 Reset Char 36 28 DT 0 = DT1 = InverseThis setting determines the type of Reset characteristic used for the IEEE/US curves.I>1 tRESET 36 29 0 From 0 to 100 step 0.01This setting determines the Reset time for the Definite Time Reset characteristic.I>2 Function 36 2A Disabled 0 = Disabled1 = DT (DT)This setting determines the tripping characteristic for the second stage overcurrent element.I>2 Current Set 36 2C 1.0*I8 From 0.08*I8 to 10.0*I8 step 0.01*I8This sets the pick-up threshold for the second stage overcurrent element.I>2 Time Delay 36 2D 1 From 0 to 100 step 0.01This sets the DT time delay for the second stage element.Terminal 9 36 30This column contains overcurrent settings for Terminal 9MiCOM P747 Chapter 5 - Protection FunctionsP747-TM-EN-1 123