GE Power ManagementL90 Line Differential Relay5-315 SETTINGS 5.3 SYSTEM SETUP55.3.6 BREAKERSPATH: SETTINGS ÖØ SYSTEM SETUP ÖØ BREAKERS Ö BREAKER 1(2)A description of the operation of the breaker control and status monitoring features is provided in the HUMAN INTER-FACES chapter. Only information concerning programming of the associated settings is covered here. These features areprovided for two breakers; a user may use only those portions of the design relevant to a single breaker, which must bebreaker No. 1.BREAKER 1 FUNCTION:Set to "Enable" to allow the operation of any breaker control feature.BREAKER1 PUSH BUTTON CONTROL:Set to "Enable" to allow faceplate push button operations.BREAKER 1 NAME: BREAKER 1BREAKER 1FUNCTION: DisabledRange: Disabled, EnabledMESSAGE BREAKER1 PUSH BUTTONCONTROL: DisabledRange: Disabled, EnabledMESSAGE BREAKER 1 NAME:Bkr 1Range: up to 6 alphanumeric charactersMESSAGE BREAKER 1 MODE:3-PoleRange: 3-Pole, 1-PoleMESSAGE BREAKER 1 OPEN:OffRange: FlexLogic™ operandMESSAGE BREAKER 1 CLOSE:OffRange: FlexLogic™ operandMESSAGE BREAKER 1 φA/3-POLE:OffRange: FlexLogic™ operandMESSAGE BREAKER 1 φB:OffRange: FlexLogic™ operandMESSAGE BREAKER 1 φC:OffRange: FlexLogic™ operandMESSAGE BREAKER 1 EXT ALARM:OffRange: FlexLogic™ operandMESSAGE BREAKER 1 ALARMDELAY: 0.000 sRange: 0.000 to 1 000 000.000 s in steps of 0.001MESSAGE BREAKER 1 OUT OF SV:OffRange: FlexLogic™ operandMESSAGE MANUAL CLOSE RECAL1TIME: 0.000 sRange: 0.000 to 1 000 000.000 s in steps of 0.001 BREAKER 2 As for Breaker 1 above UCA SBO TIMERUCA SBO TIMEOUT:30 sRange: 1 to 60 s in steps of 1