5-140L90 Line Differential RelayGE Power Management5.6 CONTROL ELEMENTS 5 SETTINGS55.6.6 DIGITAL COUNTERSPATH: SETTINGS ÖØ CONTROL ELEMENTS ÖØ DIGITAL COUNTERS Ö COUNTER 1(8)There are 8 identical digital counters, numbered from 1 to 8. A digital counter counts the number of state transitions fromLogic 0 to Logic 1. The counter is used to count operations such as the pickups of an element, the changes of state of anexternal contact (e.g. breaker auxiliary switch), or pulses from a watt-hour meter.COUNTER 1 UNITS:Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted. The units label will appearin the corresponding Actual Values status.COUNTER 1 PRESET:Sets the count to a required preset value before counting operations begin, as in the case where a substitute relay is to beinstalled in place of an in-service relay, or while the counter is running.COUNTER 1 COMPARE:Sets the value to which the accumulated count value is compared. Three FlexLogic™ output operands are provided to indi-cate if the present value is "more than (HI)", "equal to (EQL)", or "less than (LO)" the set value.COUNTER 1 UP:Selects the FlexLogic™ operand for incrementing the counter. If an enabled UP input is received when the accumulatedvalue is at the limit of +2,147,483,647 counts, the counter will rollover to –2,147,483,647.COUNTER 1 DOWN:Selects the FlexLogic™ operand for decrementing the counter. If an enabled DOWN input is received when the accumu-lated value is at the limit of -2,147,483,647 counts, the counter will rollover to +2,147,483,647. COUNTER 1COUNTER 1FUNCTION: DisabledRange: Disabled, EnabledMESSAGE COUNTER 1 NAME:Counter 1Range: 12 alphanumeric charactersMESSAGE COUNTER 1 UNITS:Range: 6 alphanumeric charactersMESSAGE COUNTER 1 PRESET:0Range: –2,147,483,647 to +2,147,483,647MESSAGE COUNTER 1 COMPARE:0Range: –2,147,483,647 to +2,147,483,647MESSAGE COUNTER 1 UP:OffRange: FlexLogic™ operandMESSAGE COUNTER 1 DOWN:OffRange: FlexLogic™ operandMESSAGE COUNTER 1 BLOCK:OffRange: FlexLogic™ operandMESSAGE CNT1 SET TO PRESET:OffRange: FlexLogic™ operandMESSAGE COUNTER 1 RESET:OffRange: FlexLogic™ operandMESSAGE COUNT1 FREEZE/RESET:OffRange: FlexLogic™ operandMESSAGE COUNT1 FREEZE/COUNT:OffRange: FlexLogic™ operand